35KV数字高压无线核相仪注意事项及保养:
1. Install antenna before frequency transmission calibration. The polycarbonate housing must be kept clean — wipe off dirt and moisture. After each use, wipe the instrument with a cloth dipped in silicone oil.
2. Store the instrument properly in its case when not in use.
3. In low temperatures (-10°C or below), store the instrument in a warm place as batteries may fail in cold conditions.
4. Test the instrument before each use.
35KV数字高压无线核相仪Technical Features:
1、屏幕显示Content:无线高压核相仪,不同相、同相、频率、X、Y、 、 、。
2、电源:主机采用可充电电源,X 和 Y 采集器 5 节 AG13 电池。
3、自动关机:开机后8分钟左右主机自动关机
4、接触被测强电场时,仪器会自动报警。
Technical Specifications:
1. In-Phase Determination: ≤15° is in-phase
2. Accuracy: Self-calibration ≤2°; Field: In-phase ≤8°, Out-of-phase ≤13°
3. Sampling Rate: 3 times/second
4. Main Unit Power: 9V±2V
5. X & Y Collector Voltage: 12V±3V
6. Host Operating Current ≤7mA
7. X & Y Collector Current: ≤5mA
8. Host to X & Y Collector Line-of-Sight Distance: X≥150m, Y≥150m
9、工作环境: -35℃┉ 50℃ 湿度:≤95%RH
10、储存环境:-40℃┉ 55℃ 湿度:≤95%RH
11. Measurable AC Voltage Range: 0.38kV~500kV